DRU-24V10ACZ
Fiche technique
- Output Current
- 10A
- Output Voltage
- 24V
- Output Voltage Range
- 23-28Vdc
- Output Power
- 240W
- Nominal Input Voltage
- 24Vdc
- Input Voltage Range
- 24-28Vdc
- Input Current
- Charging Mode: 0.5 ± 0.1A
- Case Chassis / Cover
- Plastic
- Cooling System
- Convection
- Operating Temperature
- -20°C to +60°C (full power)
- Storage Temperature
- -25°C to +85°C
- Operating Humidity
- 5 to 95% RH (Non-Condensing)
- Vibration (Non-Operating)
- IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms); 20 min per axis for all X, Y, Z directions
- Degree of Protection
- IP20
- CE
- In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
- Vibration (Operating)
- IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions
- Shock Test (Non-Operating)
- IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11ms, 3 time per direction, 9 times in total
- Overvoltage
- Buffering Mode: 33Vdc Max will not cause damage to the unit, Latch Mode
- Short Circuit
- Buffering Mode: Shutdown, Latch-off Mode
- Protection Against Shock
- Class III
- Galvanic Isolation
- Power Port to Signal Port: 1.0KVac
- Operating Altitude
- 0 to 3,000 Meters (9,840 ft)
- Safety Entry Low Voltage
- SELV (EN 60950-1)
- Immunity
- EN/BS EN 55024, EN/BS EN 61000-6-2
- DC Input Voltage Range
- 24-28 Vdc
- Shock Test (Operating)
- IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 time per direction, 9 times in total
- Pollution Degree
- 2
- Industrial Control Equipment
- UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
- Mounting Rail
- Standard TS35 DIN Rail in accordance with EN 60715
- Electrical Equipments of Machines
- EN/BS EN 60204-1
- Electrical Equipment for Use in Electrical Power Installations
- IEC/EN/BS EN 62477-1/IEC 62103
- BIS
- IS 13252-1
- Buffering Time
- Approx. 37 min at 24V/10A with 12AH battery
- Wrong Battery Voltage Protection
- Shutdown, 35V Max (the maximum voltage that will not cause damage to the unit)
- Deep Discharge Protection
- Yes (22V ± 1V)