MDS-400ADB24 AB
Ficha técnica
- Output Current
- 16.67A
- Output Voltage
- 24V
- Output Power
- 400W
- Line Regulation
- ±0.5%
- Load Regulation
- ±1%
- Start-up Time
- 2000ms @ 115Vac
- Hold-up Time
- 10ms@115Vac, with 400W load
- Dynamic Response (Overshoot and Undershoot O/P Voltage)
- ± 5% @ with 50-100% load
- Nominal Input Voltage
- 100-240Vac
- Input Voltage Range
- 90-264Vac
- Nominal Input Frequency
- 50-60Hz
- Input Frequency Range
- 47-63Hz
- Input Current
- 5.5A
- Case Chassis / Cover
- Enclosed cover(SPCC)
- Storage Temperature
- -40°C to +85°C
- Operating Humidity
- 5-95% RH (Non-Condensing)
- Shock Test (Non-Operating)
- 50G, 11ms, 3 shocks for each direction
- Operating Altitude
- 5,000 meters (16402 feet)
- Overvoltage
- 135% of rated voltage, Latch Mode
- Over Temperature
- Latch Mode
- Short Circuit
- Hiccup Mode, (Non-Latching, Auto-Recovery)
- MTBF
- 500 Khrs based on Telecordia SR-332
- Emission
- EN/BS EN 55011 & compliant with EN/BS EN 55032, FCC Title 47:Class B
- Harmonic Current Emissions
- IEC61000-3-2 Meet Class D limit
- Rise Time
- 100ms
- Power Factor at 100% load
- 0.95 @ 115V/50Hz, 230V/50Hz, full load
- Power De-rating
- Linearly derate from 100% load at 50°C, to 50% load at 70°C (2.5%/ degree centigrade)
- Expected Cap Life Time
- 16CFM Air Flow 500 kHrs based on Telecordia SR-332 Operating life at 115Vac, 400W, ambient 25 °C, 16CFM Air Flow: 26,280Hrs
- Voltage Fluctuation and Flicker
- IEC61000-3-3
- Inrush Current
- 40A@230Vac, cold start
- Vibration (Operating)
- 5-500Hz, 2Grms, 15 minute for each three axis
Nuevo