DRB-24V040ABN
Ficha técnica
- Output Current
- 40A
- Output Voltage
- 24V
- Nominal Input Voltage
- 24Vdc
- Input Voltage Range
- 22.8-28.8Vdc
- Input Power (Standby Mode)
- 2.5W
- Case Chassis / Cover
- Aluminium
- Cooling System
- Convection
- Operating Temperature
- -25°C to +75°C
- Storage Temperature
- -25°C to +85°C
- Operating Humidity
- 5 to 95% RH (Non-Condensing)
- Vibration (Non-Operating)
- IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction
- Degree of Protection
- IP20
- Expected Cap Life Time
- 10 years (Standby Mode @ 40°C)
- CE
- In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
- Harmonic Current Emissions
- IEC/EN/BS EN 61000-3-2, Class A
- Voltage Fluctuation and Flicker
- IEC/EN/BS EN 61000-3-3
- Shock Test (Non-Operating)
- IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
- Overvoltage
- Yes, 35Vdc Max (the maximum input voltage that will not cause damage to the unit)
- Short Circuit
- Yes, No damage to the unit, Latch-off Mode
- Protection Against Shock
- Class I with Primary Earth connection
- Operating Altitude
- 0 to 2,500 Meters (8,200 ft.)
- Immunity
- Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
- Pollution Degree
- 2
- Component Power Supply for General Use
- EN 61204-3
- Mounting Rail
- Standard TS35 DIN Rail in accordance with EN 60715
- Electrical Equipments of Machines
- EN/BS EN 60204-1
- Electrical Equipment for Use in Electrical Power Installations
- IEC/EN/BS EN 62477-1 / IEC 62103
- Buffering Time
- 200ms Min @ 24V/40A Load, 8s Min @ 24V/1A Load
Nuevo
No customer reviews for the moment.