PMT-24V200W2BR
Sheet
- Output Current
- 0-8.8A
- Output Voltage
- 24V
- Output Power
- 211.2W
- Nominal Input Voltage
- 100-120 Vac, 200-240 Vac (Selectable by Switch)
- Input Voltage Range
- 90-132 Vac, 180-264 Vac (Selectable by Switch)
- Nominal Input Frequency
- 50-60 Hz
- Input Frequency Range
- 47-63Hz
- Efficiency at 100% load
- 90% typ. @230 Vac
- Inrush Current
- 60 A typ. @ 230 Vac
- Case Chassis / Cover
- Aluminum / SGCC
- Cooling System
- Convection
- Operating Temperature
- -40°C to +70°C
- Storage Temperature
- -40°C to +85°C
- Operating Humidity
- 20 to 90% RH (Non-Condensing)
- Vibration (Non-Operating)
- IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction
- Expected Cap Life Time
- 10 years (230 Vac, 50% load @ 40°C)
- UKCA
- In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016
- Harmonic Current Emissions
- IEC/EN/ BS EN 61000-3-2 Class A
- Load Regulation
- ± 0.5% typ. @ 100-132 Vac, 180-264 Vac (Selectable by Switch)
- Start-up Time
- 500 ms typ. @ 115 Vac & 230 Vac
- Hold-up Time
- 30 ms typ. @ 115 Vac & 230 Vac
- Vibration (Operating)
- IEC 60068-2-6, Sine Wave: 20 Hz to 500 Hz (5 G); 10 min per cycle, 60min for each axis (X, Y,Z)
- Shock Test (Non-Operating)
- IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11ms, 3 shocks for each 3 directions
- Overvoltage
- 26.4 V - 33.6 V SELV Output, Latch Mode
- Overload / Overcurrent
- 110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
- Over Temperature
- Latch Mode
- Short Circuit
- Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed)
- Protection Against Shock
- Class I with Protection Earth connection
- Output Voltage Adjustment Range
- 21.6-26.4 Vdc
- Start-up with Capacitive Loads
- 8,000 µF Max
- Wire
- AWG 18-12
- Operating Altitude
- 0 to 5,000 Meters (0 to 16,400 ft)
- Safety Entry Low Voltage
- SELV
- Immunity
- EN/BS EN 55035, KN35, EN/BS EN 61000-6-2 & Compliance to EN/BS EN 55014-2,EN/BS EN 61000-6-1
- Indicator
- Green LED (DC OK)
- Shock Test (Operating)
- IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms, 3 shock for each 3 directions.
- Pollution Degree
- 3
- Rise Time
- 30 ms typ. @ 115 Vac & 230 Vac
- Over Voltage Category
- II (Compliance to EN 62477-1 OVC III with 2000 meters altitude)
New product