Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class II (No Primary Earth connection is required)
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic Isolation
Input to Output: 3.0KVac
UKCA
In conformance with 2016 No. 1101. The Electrical Equipment (Safety) Regulations 2016 and 2016 No. 1091 The Electromagnetic Compatibility Regulations 2016
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Cooling System
Convection
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Immunity
Generic Standards: EN 55024
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Indicator
Green LED (DC OK)
Input Terminal
2 Pins (Rated 300V/25A)
Output Terminal
4 Pins (Rated 300V/25A)
Output Voltage Adjustment Range
24-28Vdc
DC Input Voltage Range
125-375Vdc
Start-up with Capacitive Loads
3,000µF Max
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Wire
Input/Output: AWG 22-12
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions
Shock Test (Operating)
IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 shocks for each 3 directions, 9 times in total
Pollution Degree
2
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E338991)