PJL-48V400WBAA
Sheet
- Output Current
- 8.33A
- Output Voltage
- 48V
- Output Power
- 400W
- Line Regulation
- ± 1% typ. (@ 100-277Vac input, 0-100% load)
- Load Regulation
- ± 2% typ. (@ 100-277Vac input, 0-100% load)
- Dynamic Response (Overshoot and Undershoot O/P Voltage)
- ± 5% @ 100-305Vac input, 0-50% load & 50-100% load & 0-100% load (Slew Rate: 2.5A/µS, 50% duty cycle @ 5Hz, 50Hz, 1KHz)
- Nominal Input Voltage
- 100-277Vac
- Input Voltage Range
- 85-305Vac
- Nominal Input Frequency
- 50-60Hz
- Input Frequency Range
- 47-63Hz
- Operating Temperature
- -40°C to +80°C
- Storage Temperature
- -40°C to +85°C
- Operating Humidity
- 5 to 95% RH (Non-Condensing)
- Shock Test (Non-Operating)
- IEC 60068-2-27, Half Sine 50G for a duration of 11ms, 3 times per direction, 9 times in total
- Vibration (Non-Operating)
- IEC 60068-2-6, 10Hz to 150Hz @ 25m/S² (2.5G peak); displacement of 0.35mm; 90 min per axis for all X, Y, Z direction
- Operating Altitude
- 0 to 5,000 Meters (16,400 ft.)
- Over Temperature
- Latch Mode
- Short Circuit
- Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
- Protection Against Shock
- Class I with Primary Earth connection
- CE
- In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
- Emission
- Generic Standards: CISPR 32, EN/BS EN 55032: Class B
- Harmonic Current Emissions
- IEC/EN/BS EN 61000-3-2, Class C
- Expected Cap Life Time
- 10 years (115Vac & 230Vac, 50% load @ 40°C)
- Immunity
- Generic Standards: EN/BS EN 55024, EN/BS EN 55035
- Voltage Fluctuation and Flicker
- IEC/EN/BS EN 61000-3-3 at nominal voltages and full load
- Output Voltage Adjustment Range
- 48-50Vdc
- Start-up with Capacitive Loads
- 680µF Max
- Pollution Degree
- 2
- Safety Entry Low Voltage
- SELV (IEC 60950-1)
- Over Voltage Category
- II
New product